Abstract

The research of electrical power quality of electrical complex of oil refinery OOO PO Kirishinefteorgsintez was carried out. The values of distortion coefficient of sinusoidal voltage curve in the network in the spectrum of harmonics 6k± 1 (5, 7, 11, 13, 17), showing that their sources are 6-pulse frequency converters of the regulated drive. The negative impact of the higher current harmonics on the electrical consumers of the oil refinery has been determined. For normalization of electromagnetic situation and reduction of non-sinusoidal voltage are proposed: schematic measures, use of filtering devices, use of special equipment, characterized by a reduced level of generation of higher harmonics in the network.

Область исследования:
(Archived) Mining electromechanics
Funding:

None

Go to volume 155

Similar articles

Calculation algorithm of layered massif to predict the stress state of the roof and the coal seam in the zone of mining operations
2003 A. P. Gospodarikov, S. V. Vasilev, M. A. Zatsepin
Ways to intensify the grinding process in cylindrical mills with steel grinding media
2003 A. M. Vasilev
Assessment of investment risk in the oil industry when designing the development of oil fields of poorly explored areas
2003 M. A. Lazarenko
On the issue of integrated assessment of spatial conditions of land use
2003 E. N. Bykova
Equilibrium recrystallization of aluminum hydroxide
2003 A. V. Starshinov, A. V. Tsybizov
Geomechanical justification of methods and means to ensure the stability of preparatory workings in zones of high rock pressure in layered massifs
2003 D. I. Raevskii