Influence of power quality deviations on parameters and characteristics of oil refinery equipment

Authors:
Yu. V. Gulkov
About authors
  • Postgraduate student G.V. Plekhanov Saint Petersburg State Mining Institute
Date submitted:
2002-06-01
Date accepted:
2002-07-14
Date published:
2003-01-01

Abstract

The research of electrical power quality of electrical complex of oil refinery OOO PO Kirishinefteorgsintez was carried out. The values of distortion coefficient of sinusoidal voltage curve in the network in the spectrum of harmonics 6k± 1 (5, 7, 11, 13, 17), showing that their sources are 6-pulse frequency converters of the regulated drive. The negative impact of the higher current harmonics on the electrical consumers of the oil refinery has been determined. For normalization of electromagnetic situation and reduction of non-sinusoidal voltage are proposed: schematic measures, use of filtering devices, use of special equipment, characterized by a reduced level of generation of higher harmonics in the network.

Область исследования:
(Archived) Mining electromechanics
Go to volume 155

Similar articles

Geomechanical justification of methods and means to ensure the stability of preparatory workings in zones of high rock pressure in layered massifs
2003 D. I. Raevskii
Socio-economic and environmental challenges of the development of the coal industry in Russia
2003 E. A. Soloveva, O. Yu. Lebedeva
Problems and prospects for Gazprom's development in the context of the formation of the Pan-European gas market
2003 A. E. Savchenko
Enhancement of ore dressing processes for copper-nickel ores
2003 M. E. Golovanov, S. V. Dmitriev
New methods of computer calculations of material balances at enrichment plants
2003 M. S. Molodtsev, A. M. Arustamyan
Experimental studies of the effectiveness of biological treatment of oil-contaminated soils
2003 E. A. Sinkova