Submit an Article
Become a reviewer
Vol 155 Iss. 1
Pages:
139-142
Download volume:
RUS
Article

Influence of power quality deviations on parameters and characteristics of oil refinery equipment

Authors:
Yu. V. Gulkov
About authors
  • Postgraduate student G.V. Plekhanov Saint Petersburg State Mining Institute
Date submitted:
2002-06-01
Date accepted:
2002-07-14
Date published:
2003-12-08

Abstract

The research of electrical power quality of electrical complex of oil refinery OOO PO Kirishinefteorgsintez was carried out. The values of distortion coefficient of sinusoidal voltage curve in the network in the spectrum of harmonics 6k± 1 (5, 7, 11, 13, 17), showing that their sources are 6-pulse frequency converters of the regulated drive. The negative impact of the higher current harmonics on the electrical consumers of the oil refinery has been determined. For normalization of electromagnetic situation and reduction of non-sinusoidal voltage are proposed: schematic measures, use of filtering devices, use of special equipment, characterized by a reduced level of generation of higher harmonics in the network.

Область исследования:
(Archived) Mining electromechanics
Funding:

None

Go to volume 155

Similar articles

Influence of changes in the Tax Code of the Russian Federation on the financial results of mineral complex enterprises of the Russian Federation
2003 R. A. Gavrilova
Faculty of Mining and Electrical Engineering. History of formation and current state
2003 A. S. Fokin
Enhancement of ore dressing processes for copper-nickel ores
2003 M. E. Golovanov, S. V. Dmitriev
Determination of pouring fluid column height when drilling deep wells in ice sediments
2003 N. S. Kononova
Methods of creating bridge geodetic networks and their technical and economic comparison
2003 N. B. Korableva
Improving the methodology of diagnosing the bankruptcy of fuel and energy companies
2003 M. N. Vakhnina