Submit an Article
Become a reviewer
Vol 155 Iss. 1
Pages:
139-142
Download volume:
RUS
Article

Influence of power quality deviations on parameters and characteristics of oil refinery equipment

Authors:
Yu. V. Gulkov
About authors
  • Postgraduate student G.V. Plekhanov Saint Petersburg State Mining Institute
Date submitted:
2002-06-01
Date accepted:
2002-07-14
Date published:
2003-12-08

Abstract

The research of electrical power quality of electrical complex of oil refinery OOO PO Kirishinefteorgsintez was carried out. The values of distortion coefficient of sinusoidal voltage curve in the network in the spectrum of harmonics 6k± 1 (5, 7, 11, 13, 17), showing that their sources are 6-pulse frequency converters of the regulated drive. The negative impact of the higher current harmonics on the electrical consumers of the oil refinery has been determined. For normalization of electromagnetic situation and reduction of non-sinusoidal voltage are proposed: schematic measures, use of filtering devices, use of special equipment, characterized by a reduced level of generation of higher harmonics in the network.

Область исследования:
(Archived) Mining electromechanics
Funding:

None

Go to volume 155

Similar articles

Creating an electronic guide to the Pascal programming language
2003 A. M. Smirnov
Challenges of predicting the methane content of the Vorkuta and Donbass analogous fields
2003 V. N. Novikova
New methods of computer calculations of material balances at enrichment plants
2003 M. S. Molodtsev, A. M. Arustamyan
Determining the coordinates of the location and number of electrical substations at the industrial site of the mining enterprise
2003 A. V. Krivenko
Equilibrium recrystallization of aluminum hydroxide
2003 A. V. Starshinov, A. V. Tsybizov
Ecological state of green spaces in Pushkin
2003 E. A. Polyakova, V. F. Kovyazin