On the need to improve the design thermal calculation of mine calorifiers
Authors:
Abstract
The shortcomings of the applied methodology of design thermal calculation of duct heaters are noted, it is shown that the replacement of the heat transfer coefficient of the plant with the heat transfer coefficient of the duct heaters can lead to an inadmissible underestimation of the required heating surface of the plant, which in extreme operating conditions will inevitably cause its freezing and failure.
Область исследования:
Mining
References
- Album of equipment. Calorifiers and units / GPI Santekhproekt. М., 1964.
- Manual on maintenance of calorifier installations of mines / Edited by N.I. Karasev. Moscow: Nedra, 1984.
- Construction catalog No. 8. Section 81. Calorifiers/Santekhnieproekt. М., 1990.
- Designer's Handbook. Ch.2. Ventilation and air conditioning / Edited by I.G. Staroverova, M.: Stroyizdat, 1977.
- Taliev V.N. Approximate method of calculation of the heat transfer coefficient of a caloriferous installation//Water supply and sanitary engineering. 1957. № 2.
Similar articles
Forecast of changes in the natural structure of the host rock ahead of longwalls (faces)
1995 A. A. Borisov
Ways to expand the output of new types of products based on titanium-magnesium production
1995 S. V. Alexandrovsky, A. I. Gulyakin